SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1459
4 Faults and alarms
4.2 List of faults and alarms
F01692
SI Motion P1 (CU): Parameter value not permitted for encoderless
Message value:
Parameter: %1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
None
Propagation:
GLOBAL
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The parameter cannot be set to this value if encoderless motion monitoring functions have been selected in p9506.
Note:
This fault does not result in a safety stop response.
Fault value (r0949, interpret decimal):
Parameter number with the incorrect value.
See also: p9501 (SI Motion enable safety functions (Control Unit))
Remedy:
- correct the parameter specified in the fault value.
- if necessary, de-select encoderless motion monitoring functions (p9506).
See also: p9501 (SI Motion enable safety functions (Control Unit))
A01693 (F)
SI P1 (CU): Safety parameter setting changed, warm restart/POWER ON required
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Component:
None
Propagation:
GLOBAL
Reaction:
NONE
Acknowledge:
NONE
Cause:
Safety parameters have been changed; these will only take effect following a warm restart or POWER ON.
Notice:
All changed parameters of the safety motion monitoring functions will only take effect following a warm restart or
POWER ON.
Alarm value (r2124, interpret decimal):
Parameter number of the safety parameter which has changed, necessitating a warm restart or POWER ON.
Remedy:
- carry out a warm restart (p0009 = 30, p0976 = 2, 3).
- carry out a POWER ON (switch-off/switch-on) for all components.
Note:
Before performing an acceptance test, a POWER ON must be carried out for all components.
Reaction upon F:
Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F:
POWER ON
F01694 (A)
SI Motion CU: Firmware version Motor Module/Hydraulic Module older Control Unit
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
None
Propagation:
GLOBAL
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The firmware version of the Motor Module/Hydraulic Module is older than the version of the Control Unit.
It is possible that safety functions are not available (r9771/r9871).
Note:
This message does not result in a safety stop response.
This message can also occur, if after an automatic firmware update, a POWER ON was not carried out (Alarm
A01007).
Remedy:
Upgrade the firmware of the Motor Module/Hydraulic Module to a later version.
See also: r9390 (SI Motion version safety motion monitoring (Motor Module)), r9590 (SI Motion version safety motion
monitoring (Control Unit))
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......