2 Parameters
2.2 List of parameters
SINAMICS G130/G150
816
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the communication parameters for CANopen Receive Process Data Object 3 (RPDO 3).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Note:
Corresponds to the CANopen object 1402 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
Description:
Sets the communication parameters for CANopen Receive Process Data Object 4 (RPDO 4).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Note:
Corresponds to the CANopen object 1403 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
Description:
Sets the communication parameters for CANopen Receive Process Data Object 5 (RPDO 5).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Note:
Corresponds to the CANopen object 1404 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
p8702[0...1]
CAN Receive PDO 3 / Receive PDO 3
VECTOR_G (CAN)
Can be changed:
C1(3), T
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
9204, 9206
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0000 hex
8000 06DF hex
[0] 8000 06DF hex
[1] 00FE hex
p8703[0...1]
CAN Receive PDO 4 / Receive PDO 4
VECTOR_G (CAN)
Can be changed:
C1(3), T
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
9204, 9206
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0000 hex
8000 06DF hex
[0] 8000 06DF hex
[1] 00FE hex
p8704[0...1]
CAN Receive PDO 5 / Receive PDO 5
VECTOR_G (CAN)
Can be changed:
C1(3), T
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
9204
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0000 hex
8000 06DF hex
[0] 8000 06DF hex
[1] 00FE hex
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......