2 Parameters
2.2 List of parameters
Note:
When the ground fault monitoring initiates a fault for overlapping synchronizing the threshold value p0287[1] for the
Motor Module and the associated infeed must be appropriately increased (e.g. p0287[1] = 100 %).
For p3800 = 1, the following applies:
The INTERNAL voltage actual values are used for synchronization. The effects that a (sine-wave) filter - that is
connected between the Motor Module and motor - has on the voltage actual values are taken into account
(theoretically) by appropriately selecting p0230.
VSM: Voltage Sensing Module
Description:
Sets the drive object number of the VSM used for the line-drive synchronization.
Dependency:
Refer to: p3800, p3802
Notice:
The current controller sampling time p0115[0] of the drive object with the VSM used for synchronization must be
identical to the current controller sampling time of the drive of the drive used to perform line synchronization.
Note:
VSM: Voltage Sensing Module
The setting p3801 = 1 is always possible (no VSM selected).
If the VSM is assigned subsequently to a Motor Module, its drive object number must be entered in p3801.
The line voltage is always measured using the first VSM (p0151[0]).
Description:
Sets the signal source to switch in/switch out for the line-drive synchronization.
BI: p3802 = 1 signal:
The line-drive synchronization is switched in.
Dependency:
Refer to: p3800, p3801
Description:
Displays the control word for the line-drive synchronization.
Note:
For bit 00:
For a 1 signal, p3800 > 0 is set.
p3801[0...n]
Sync-line-drive drive object number / Sync DO_no
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
DDS, p0180
Func. diagram:
7020
P-Group:
Functions
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1 62
1
p3802[0...n]
BI: Sync-line-drive enable / Sync enable
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
7020
P-Group:
Functions
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
r3803.0
CO/BO: Sync-line-drive control word / Sync STW
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
Functions
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Sync-line-drive selected
Yes
No
-
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......