2 Parameters
2.2 List of parameters
SINAMICS G130/G150
1004
List Manual (LH2), 07/2016, A5E03263479A
It is not permissible to parameterize "motor holding brake without feedback signals" and also enable "safe brake
control" (p1278 = 1, p9602 = 1, p9802 = 1).
MM: Motor Module
SBC: Safe Brake Control
SI: Safety Integrated
Description:
Sets the PROFIsafe address of the Motor Module/Hydraulic module.
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Description:
Sets the PROFIsafe telegram number for the Motor Module/Hydraulic Module.
Value:
0:
No PROFIsafe telegram selected
30:
PROFIsafe standard telegram 30, PZD-1/1
31:
PROFIsafe standard telegram 31, PZD-2/2
900:
PROFIsafe SIEMENS telegram 900, PZD-2/2
901:
PROFIsafe SIEMENS telegram 901, PZD-3/5
902:
PROFIsafe SIEMENS telegram 902, PZD-3/6
998:
Compatibility mode (as for firmware version < 4.5)
Dependency:
Refer to: p9611, p60022
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
For p9601.3 = p9801.3 = 1 (PROFIsafe enabled), the following variants exist when parameterizing PROFIsafe
telegram 30:
- p9611 = p9811 = 998 and p60022 = 0
- p9611 = p9811 = 998 and p60022 = 30
- p9611 = p9811 = 30 and p60022 = 30
Description:
Sets the stop response when PROFIsafe communication fails.
Value:
0:
STOP A
1:
STOP B
Dependency:
Refer to: p9612
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
p9810
SI PROFIsafe address (Motor Module) / SI PROFIsafe MM
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 65534
0
p9811
SI PROFIsafe telegram selection (Motor Module) / SI Ps telegram MM
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 998
998
p9812
SI PROFIsafe failure response (Motor Module) / SI Ps fail MM
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......