2 Parameters
2.2 List of parameters
SINAMICS G130/G150
526
List Manual (LH2), 07/2016, A5E03263479A
For p0922 = 999 the following applies:
p2079 can be freely set. If p2079 is also set to 999, then all of the interconnections can be set.
For p0922 = 999 and p2079 < 999 the following applies:
The interconnections contained in the telegram are inhibited. However, the telegram can be extended.
Description:
Sets the send and receive telegram.
Contrary to p0922, a telegram can be selected using p2079 and subsequently expanded.
Value:
1:
Standard telegram 1, PZD-2/2
2:
Standard telegram 2, PZD-4/4
20:
Standard telegram 20, PZD-2/6
220:
SIEMENS telegram 220, PZD-10/10
352:
SIEMENS telegram 352, PZD-6/6
999:
Free telegram configuration with BICO
Dependency:
Refer to: p0922
Note:
For p0922 < 999 the following applies:
p2079 has the same value and is inhibited. All of the interconnections and extensions contained in the telegram are
inhibited.
For p0922 = 999 the following applies:
p2079 can be freely set. If p2079 is also set to 999, then all of the interconnections can be set.
For p0922 = 999 and p2079 < 999 the following applies:
The interconnections contained in the telegram are inhibited. However, the telegram can be extended.
Description:
Sets the send and receive telegram.
Contrary to p0922, a telegram can be selected using p2079 and subsequently expanded.
Value:
1:
Standard telegram 1, PZD-2/2
2:
Standard telegram 2, PZD-4/4
3:
Standard telegram 3, PZD-5/9
4:
Standard telegram 4, PZD-6/14
20:
Standard telegram 20, PZD-2/6
220:
SIEMENS telegram 220, PZD-10/10
352:
SIEMENS telegram 352, PZD-6/6
999:
Free telegram configuration with BICO
Dependency:
Refer to: p0922
Note:
For p0922 < 999 the following applies:
p2079 has the same value and is inhibited. All of the interconnections and extensions contained in the telegram are
inhibited.
For p0922 = 999 the following applies:
p2079 can be freely set. If p2079 is also set to 999, then all of the interconnections can be set.
For p0922 = 999 and p2079 < 999 the following applies:
The interconnections contained in the telegram are inhibited. However, the telegram can be extended.
p2079
IF1 PROFIdrive PZD telegram selection extended / IF1 PZD telegr ext
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1 999
999
p2079
IF1 PROFIdrive PZD telegram selection extended / IF1 PZD telegr ext
VECTOR_G (n/M)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1 999
999
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......