2 Parameters
2.2 List of parameters
Description:
Enters the capacitance of a sine-wave filter connected at the power unit output.
Dependency:
This parameter is automatically pre-set when you select a filter via p0230 if a SIEMENS filter is defined for the power
unit.
Refer to: p0230
Note:
The parameter value includes the sum of all of the capacitances of a phase connected in series (phase - ground).
When exiting the quick commissioning using p3900 = 1, the parameter value is set to the value of the defined
SIEMENS filter or to zero. For this reason, the parameter value of a third-party filter only has to be entered outside
the commissioning phase (p0010 = 0).
Description:
Sets the number of reactors connected in series at the power unit output.
Dependency:
Refer to: p0230
Notice:
If the number of motor reactors connected in series does not correspond to this parameter value, then this can result
in an unfavorable control behavior.
Description:
Displays the internal resistance of the power unit (IGBT and line resistance).
Note:
For a parallel circuit, the value corresponds to the resistance of a power unit.
Description:
Sets the configuration for the voltage measurement.
p0234
Power unit sine-wave filter capacitance / PU sine filter C
VECTOR_G
Can be changed:
C2(2), U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Converter
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [µF]
1000.000 [µF]
0.000 [µF]
p0235
Motor reactor in series number / L_mot in SeriesQty
VECTOR_G
Can be changed:
C2(1, 2)
Calculated:
-
Access level:
1
Data type:
Unsigned8
Dyn. index:
-
Func. diagram:
-
P-Group:
Converter
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1 3
1
r0238
Internal power unit resistance / PU R internal
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Converter
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- [ohm]
- [ohm]
- [ohm]
p0247
Voltage measurement configuration / U_mes config
VECTOR_G
Can be changed:
C2(2), U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
Converter
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-
-
0000 0000 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
05
Use voltage measured values for flying
restart
Yes
No
-
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......