4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1396
List Manual (LH2), 07/2016, A5E03263479A
General note:
The topology rules should be noted when connecting up DRIVE-CLiQ (refer to the appropriate product
documentation).
The parameters of the sampling times can also be changed with automatic calculations.
Example for highest common denominator: 125 s, 125 µs, 62.5 µs --> 62.5 µs
Remedy:
- check the DRIVE-CLiQ cables.
- set a valid sampling time.
See also: p0115, p0799, p4099
A01224
CU: Pulse frequency inconsistent
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
None
Propagation:
LOCAL
Reaction:
NONE
Acknowledge:
NONE
Cause:
When changing the minimum pulse frequency (p0113) inconsistency between the pulse frequencies was identified.
Alarm value (r2124, interpret decimal):
1: Value lower than minimum value.
2: Value higher than maximum value.
3: Resulting sampling time is not a multiple of 1.25 µs.
4: Value does not match clock-cycle synchronous PROFIBUS operation.
10: Special restriction of the drive object violated.
99: Inconsistency of cross drive objects detected.
116: Recommended clock cycle in r0116[0...1].
Remedy:
Set a valid pulse frequency.
See also: p0113 (Minimum pulse frequency, selection)
F01250
CU: CU-EEPROM incorrect read-only data
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
All objects
Component:
Control Unit (CU)
Propagation:
LOCAL
Reaction:
NONE (OFF2)
Acknowledge:
POWER ON
Cause:
Error when reading the read-only data of the EEPROM in the Control Unit.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON.
- replace the Control Unit.
A01251
CU: CU-EEPROM incorrect read-write data
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
All objects
Component:
Control Unit (CU)
Propagation:
GLOBAL
Reaction:
NONE
Acknowledge:
NONE
Cause:
Error when reading the read-write data of the EEPROM in the Control Unit.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
For alarm value r2124 < 256, the following applies:
- carry out a POWER ON.
- replace the Control Unit.
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......