SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
377
2 Parameters
2.2 List of parameters
Description:
Sets the signal source for the voltage setpoint for U/f control with an independent voltage setpoint (p1300 = 19).
Dependency:
Selects the U/f control with independent voltage setpoint via p1300 = 19.
Refer to: p1300
Description:
Limiting the voltage setpoint.
This means that the output voltage can be reduced with respect to the calculated maximum voltage r0071 and the
start of field weakening.
Note:
The output voltage is only limited if, as a result of p1331, the maximum output voltage (r0071) is fallen below.
Description:
Sets the starting frequency at which FCC (Flux Current Control) is activated.
Dependency:
The correct operating mode must be set (p1300 = 1, 6).
Warning:
An excessively low value can result in instability.
Note:
For p1333 = 0 Hz, the FCC starting frequency is automatically set to 6 % of the rated motor frequency.
Description:
Sets the starting frequency of the slip compensation.
Note:
For p1334 = 0, the starting frequency of the slip compensation is automatically set to 6 % of the rated motor
frequency.
p1330[0...n]
CI: U/f control independent voltage setpoint / Uf U_set independ.
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
6301
P-Group:
V/f open-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
p2001
Expert list:
1
Min Max
Factory
setting
- -
0
p1331[0...n]
Voltage limiting / U_lim
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6300
P-Group:
-
Unit group:
5_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
50.00 [Vrms]
2000.00 [Vrms]
1000.00 [Vrms]
p1333[0...n]
U/f control FCC starting frequency / U/f FCC f_start
VECTOR_G
Can be changed:
U, T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6301
P-Group:
V/f open-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [Hz]
3000.00 [Hz]
0.00 [Hz]
p1334[0...n]
U/f control slip compensation starting frequency / Slip comp start
VECTOR_G
Can be changed:
U, T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6310
P-Group:
V/f open-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [Hz]
3000.00 [Hz]
0.00 [Hz]
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......