SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
263
2 Parameters
2.2 List of parameters
Index:
[0] = T0
[1] = T1
[2] = T2
Note:
Limiting on:
If signals are output outside the permissible measuring range, the signal is limited to 4.98 V or to 0 V.
Limiting off:
If signals are output outside the permissible measuring range, this causes signal overflow. In the case of signal
overflow, the signal jumps from 0 V to 4.98 V or from 4.98 V to 0 V.
Description:
Displays the scaling of the signal to be output.
A change in the output voltage by 1 volt corresponds to the value in this parameter. The units are determined by the
interconnected test signal.
Index:
[0] = T0
[1] = T1
[2] = T2
Dependency:
Refer to: p0771, r0772, r0774, p0777, p0778, p0779, p0780, p0783, p0784
Note:
Example:
r0786[0] = 1500.0 and the measuring signal is r0063 (CO: Actual speed smoothed [rpm]).
A change of 1 V at the output of test socket T0 corresponds to 1500.0 [rpm].
Description:
Sets the physical address to output signals via the test sockets.
Index:
[0] = T0
[1] = T1
[2] = T2
Dependency:
Changes only become effective if p0776 does not equal 99.
Refer to: p0789, r0790
Description:
Sets the gain of a signal output of a physical address via test sockets.
Index:
[0] = T0
[1] = T1
[2] = T2
Dependency:
Changes only become effective if p0776 does not equal 99.
Refer to: p0788
r0786[0...2]
Test socket scaling per volt / TestSktScale/Volt
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
8134
P-Group:
Terminals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
p0788[0...2]
Test sockets physical address / Test skt PhyAddr
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
Terminals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0000 bin
1111 1111 1111 1111 1111 1111
1111 1111 bin
0000 bin
p0789[0...2]
Test sockets physical address gain / TestSktPhyAddrGain
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Terminals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-340.28235E36 340.28235E36
1.00000
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......