SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1563
4 Faults and alarms
4.2 List of faults and alarms
A07478 (F)
EPOS: Target position > software limit switch plus
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
None
Propagation:
GLOBAL
Reaction:
NONE
Acknowledge:
NONE
Cause:
In the actual traversing operation, the target position is greater than the software limit switch plus.
Remedy:
- correct the target position.
- change software limit switch plus (CI: p2579, p2581).
Reaction upon F:
OFF1 (OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
A07479
EPOS: Software limit switch minus reached
Message value:
-
Message class:
Application/technological function faulted (17)
Drive object:
VECTOR_G
Component:
None
Propagation:
GLOBAL
Reaction:
NONE
Acknowledge:
NONE
Cause:
The axis is at the position of the software limit switch minus. An active traversing block was interrupted.
Remedy:
- correct the target position.
- change software limit switch minus (CI: p2578, p2580).
A07480
EPOS: Software limit switch plus reached
Message value:
-
Message class:
Application/technological function faulted (17)
Drive object:
VECTOR_G
Component:
None
Propagation:
GLOBAL
Reaction:
NONE
Acknowledge:
NONE
Cause:
The axis is at the position of the software limit switch plus. An active traversing block was interrupted.
Remedy:
- correct the target position.
- change software limit switch plus (CI: p2579, p2581).
F07481 (A)
EPOS: Axis position < software limit switch minus
Message value:
-
Message class:
Application/technological function faulted (17)
Drive object:
VECTOR_G
Component:
None
Propagation:
GLOBAL
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The actual position of the axis is less than the position of the software limit switch minus.
Remedy:
- correct the target position.
- change software limit switch minus (CI: p2578, p2580).
Reaction upon A:
NONE
Acknowl. upon A:
NONE
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......