2 Parameters
2.2 List of parameters
SINAMICS G130/G150
474
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the configuration for the test pulse evaluation.
Bit 00: Check for conductor-to-conductor short circuit once/always when the pulses are enabled.
Bit 01: Check for ground fault once/always when the pulses are enabled.
Bit 02: Activation of the tests selected using bit 00 and/or bit 01 each time the pulses are enabled
Recommendation:
If the ground fault test is incorrectly initiated because the motor is not at a complete standstill, then the pulse
cancellation delay time (p1228) should be increased.
Dependency:
The ground fault test is only possible when the motor is stationary, and is therefore only realized when flying restart is
deactivated (p1200 = 0).
When a sine-wave filter is connected, the short-circuit and the ground fault test are deactivated, as the filter could be
excited by the test pulse.
Refer to: p0287
Note:
If a conductor-to-conductor short-circuit is detected during the test, this is displayed in r1902.1.
If a ground fault is detected during the test, this is displayed in r1902.2.
For bit 02 = 0:
If the test was successful once after POWER ON (see r1902.0), it is not repeated.
For bit 02 = 1:
The test is not only performed after POWER ON, but also each time the pulses are enabled.
Description:
Displays the status of the test pulse evaluation.
Note:
If the ground fault test was selected, but not successfully performed, then sufficient current was not be able to be
established during the test pulses.
For bit 04:
A test pulse longer than one sampling time has occurred
p1901
Test pulse evaluation configuration / Test puls config
VECTOR_G
Can be changed:
T
Calculated:
CALC_MOD_ALL
Access level:
2
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
Motor identification
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Phase short-circuit test pulse active
Yes
No
-
01
Ground fault detection test pulse active
Yes
No
-
02
Test pulse at each pulse enable
Yes
No
-
r1902
Test pulse evaluation status / Test puls ev stat
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Short-circuit test successfully performed
Yes
No
-
01
Phase short-circuit detected
Yes
No
-
02
Ground fault test successfully performed
Yes
No
-
03
Ground fault detected
Yes
No
-
04
Identification pulse width greater than the
minimum pulse width
Yes
No
-
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......