4 Faults and alarms
4.2 List of faults and alarms
A49204 (N)
Excitation switch-off alarm
Message value:
-
Message class:
Hardware/software error (1)
Drive object:
VECTOR_G
Component:
Control Unit (CU)
Propagation:
GLOBAL
Reaction:
NONE
Acknowledge:
NONE
Cause:
When switching off the excitation, after the delay time (p1647) has expired, the excitation current has still not
decayed to zero.
Remedy:
Extend the switch-off delay time in (p1647).
Note:
The alarm is automatically reset after adapting p1647.
See also: p1647 (Excitation switch-off delay time)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A49998
Recorder trigger event occurred
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
B_INF, VECTOR_G
Component:
None
Propagation:
GLOBAL
Reaction:
NONE
Acknowledge:
NONE
Cause:
A recorder trigger event has occurred. The data are then written to the memory card, specifying the event number.
Alarm value (r2124, interpret decimal):
Event number.
Remedy:
Not necessary.
This message disappears automatically.
A50001 (F)
PN/COMM BOARD: Configuration error
Message value:
%1
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Component:
None
Propagation:
LOCAL
Reaction:
NONE
Acknowledge:
NONE
Cause:
CBE20:
A PROFINET controller attempts to establish a connection using an incorrect configuring telegram. The "Shared
Device" function has been activated (p8829 = 2).
Alarm value (r2124, interpret decimal):
10: A CPU sends a PROFIsafe telegram.
11: F CPU sends a PZD telegram.
12: F CPU without an A CPU.
13: F CPU with more PROFIsafe subslots than activated with p9601.3.
14: F CPU with fewer PROFIsafe subslots than activated with p9601.3.
15: PROFIsafe telegram of the F-CPU does not match the setting in p60022.
See also: p8829 (CBE2x remote controller number), p9601 (SI enable functions integrated in the drive (Control Unit))
Remedy:
CBE20:
Check the configuration of the PROFINET controllers as well as the p8829 and p9601.3 setting.
Reaction upon F:
Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F:
IMMEDIATELY
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......