4 Faults and alarms
4.2 List of faults and alarms
Note:
In general, the copy protection can only be changed when know-how protection is deactivated.
KHP: Know-How Protection
See also: p3981 (Acknowledge drive object faults), p7765 (KHP configuration)
F13101
Know-how protection: Copy protection cannot be activated
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
Control Unit (CU)
Propagation:
LOCAL
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
An error occurred when attempting to activate the copy protection for the memory card.
Fault value (r0949, interpret decimal):
0: A memory card is not inserted.
Note:
KHP: Know-How Protection
Remedy:
- insert the memory card and carry out POWER ON.
- Try to activate copy protection again (p7765).
See also: p7765 (KHP configuration)
F13102
Know-how protection: Consistency error of the protected data
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
Control Unit (CU)
Propagation:
GLOBAL
Reaction:
OFF1
Acknowledge:
IMMEDIATELY
Cause:
An error was identified when checking the consistency of the protected files. As a consequence, the project on the
memory card cannot be run.
Fault value (r0949, interpret hexadecimal):
yyyyxxxx hex: yyyy = object number, xxxx = fault cause
xxxx = 1:
A file has a checksum error.
xxxx = 2:
The files are not consistent with one another.
xxxx = 3:
The project files, which were loaded into the file system via load (download from the memory card), are inconsistent.
Note:
KHP: Know-How Protection
Remedy:
- Replace the project on the memory card or replace project files for download from the memory card.
- Restore the factory setting and download again.
F30001
Power unit: Overcurrent
Message value:
Fault cause: %1 bin
Message class:
Power electronics faulted (5)
Drive object:
B_INF, VECTOR_G
Component:
Power Module
Propagation:
LOCAL
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The power unit has detected an overcurrent condition.
- closed-loop control is incorrectly parameterized.
- motor has a short-circuit or fault to ground (frame).
- U/f operation: Up ramp set too low.
- U/f operation: Rated motor current is significantly greater than that of the Motor Module.
- infeed: High discharge and post-charging currents for voltage dip.
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......