4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1654
List Manual (LH2), 07/2016, A5E03263479A
A30016 (N)
Power unit: Load supply switched out
Message value:
%1
Message class:
Network fault (2)
Drive object:
VECTOR_G
Component:
Power Module
Propagation:
GLOBAL
Reaction:
NONE
Acknowledge:
NONE
Cause:
The DC link voltage is too low.
Alarm value (r2124, interpret decimal):
DC link voltage at the time of trip [0.1 V].
Remedy:
- switch on load supply.
- check the line supply if necessary.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F30017
Power unit: Hardware current limit has responded too often
Message value:
Fault cause: %1 bin
Message class:
Power electronics faulted (5)
Drive object:
B_INF, VECTOR_G
Component:
Power Module
Propagation:
LOCAL
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The hardware current limitation in the relevant phase (see A30031, A30032, A30033) has responded too often. The
number of times the limit has been exceeded depends on the design and type of power unit.
For infeed units, the following applies:
- closed-loop control is incorrectly parameterized.
- load on the infeed is too high.
- Voltage Sensing Module incorrectly connected.
- line reactor missing or the incorrect type.
- power unit defective.
The following applies to Motor Modules:
- closed-loop control is incorrectly parameterized.
- fault in the motor or in the power cables.
- the power cables exceed the maximum permissible length.
- motor load too high
- power unit defective.
Fault value (r0949, interpret binary):
Bit 3: phase U
Bit 4: phase V
Bit 5: phase W
Additional bits:
Only for internal Siemens troubleshooting.
Note:
Fault value = 0 means that the phase with current limiting is not recognized (e.g. for blocksize device).
Remedy:
For infeed units, the following applies:
- check the controller settings and reset and identify the controller if necessary (p0340 = 2, p3410 = 5)
- reduce the load and increase the DC link capacitance or use a higher-rating infeed if necessary
- check the connection of the optional Voltage Sensing Module
- check the connection and technical data of the line reactor
- check the power cables for short-circuit or ground fault.
- replace power unit.
The following applies to Motor Modules:
- check the motor data and if required, recalculate the controller parameters (p0340 = 3). As an alternative, run a
motor data identification (p1910 = 1, p1960 = 1).
- check the motor circuit configuration (star-delta).
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......