SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
109
2 Parameters
2.2 List of parameters
Description:
Freely assignable name for a drive object.
In the commissioning software, this name cannot be entered using the expert list, but is specified in the configuration
assistant. The object name can be subsequently modified in the Project Navigator using standard Windows
resources.
Note:
The parameter is not influenced by setting the factory setting.
Description:
Displays the unique code number of the power unit.
Note:
r0200 = p0201: No power unit found
For parallel circuit configurations, the parameter index is assigned to a power unit.
Description:
Sets the actual code number from r0200 to acknowledge the power unit being used.
When commissioned for the first time, the code number is automatically transferred from r0200 into p0201.
Dependency:
Refer to: F07815
Notice:
When p0201 = 10000, the rated power unit data is reloaded and dependent parameters are set (e.g. p0205, p0210,
p0230, p0857, p1800). p0201 is then automatically assigned the value of r0200 if the code number of the power unit
could be read. A warm start must be performed after this procedure (automatically if necessary).
Note:
The parameter is used to identify when the drive is being commissioned for the first time.
The power unit commissioning can only be exited (p0201 = r0200), if the actual and acknowledged code numbers are
identical (p0010 = 2). However, if the comparator in p9906 or p9908 is at 2 (low) or 3 (minimum), the power unit
commissioning is automatically set to p0201 = r0200 upon exiting.
When the code number is changed, the connection voltage (p0210) is checked and, if necessary, adjusted.
For parallel circuit configurations, the parameter index is assigned to a power unit.
Description:
Sets the actual code number from r0200 to acknowledge the power unit being used.
When commissioned for the first time, the code number is automatically transferred from r0200 into p0201.
p0199[0...24]
Drive object name / DO name
All objects
Can be changed:
C1
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 65535
0
r0200[0...n]
Power unit code number actual / PU code no. act
VECTOR_G, B_INF
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
PDS, p0120
Func. diagram:
-
P-Group:
Converter
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
p0201[0...n]
Power unit code number / PU code no
VECTOR_G
Can be changed:
C2(2)
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
PDS, p0120
Func. diagram:
-
P-Group:
Converter
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 65535
0
p0201[0...n]
Power unit code number / PU code no
B_INF
Can be changed:
C2(2)
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
PDS, p0120
Func. diagram:
-
P-Group:
Converter
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 65535
0
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......