4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1398
List Manual (LH2), 07/2016, A5E03263479A
F01303
Component does not support the required function
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
None
Propagation:
BICO
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A function requested by the Control Unit is not supported by a DRIVE-CLiQ component.
Fault value (r0949, interpret decimal):
1: The component does not support the deactivation.
101: The Motor Module does not support an internal armature short-circuit.
102: The Motor Module does not support the deactivation.
201: The Sensor Module does not support actual value inversion (p0410.0 = 1) when using a Hall sensor (p0404.6 =
1) for the commutation.
202: The Sensor Module does not support parking/unparking.
203: The Sensor Module does not support the deactivation.
204: The firmware of this Terminal Module 15 (TM15) does not support the application TM15DI/DO.
205: The Sensor Module does not support the selected temperature evaluation (r0458, r0459).
206: The firmware of this Terminal Modules TM41/TM31/TM15 refers to an old firmware version. It is urgently
necessary to upgrade the firmware to ensure disturbance-free operation.
207: The power unit with this hardware version does not support operation with device supply voltages of less than
380 V.
208: The Sensor Module does not support de-selection of commutation with zero mark (via p0430.23).
211: The Sensor Module does not support single-track encoders (r0459.10).
212: The Sensor Module does not support LVDT sensors (p4677.0).
213: The Sensor Module does not support the characteristic type (p4662).
214: The power unit does not support the temperature evaluation via PT1000 (r0193).
215: The Terminal Module does not support the temperature evaluation via PT1000
216: The Voltage Sensing Module (VSM) does not support operation with a PT1000 temperature sensor.
Remedy:
Upgrade the firmware of the DRIVE-CLiQ component involved.
For fault value = 205, 214, 215:
- check parameter p0600 and p0601 and if required, adapt.
For fault value = 207:
- replace the power unit or if required set the device supply voltage higher (p0210).
For fault value = 208:
- check parameter p0430.23 and reset if necessary.
For fault value = 216:
- check the setting of the sensor type (p3665).
- use a Voltage Sensing module that supports operation with PT1000 (MLFB ...-xxx1).
A01304 (F)
Firmware version of DRIVE-CLiQ component is not up-to-date
Message value:
%1
Message class:
General drive fault (19)
Drive object:
All objects
Component:
None
Propagation:
LOCAL
Reaction:
NONE
Acknowledge:
NONE
Cause:
The non-volatile memory has a more recent firmware version than the one in the connected DRIVE-CLiQ
component.
Alarm value (r2124, interpret decimal):
Component number of the DRIVE-CLiQ component involved.
Remedy:
Update the firmware (p7828, p7829 and commissioning software).
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......