2 Parameters
2.2 List of parameters
Note:
The test sequence is selected using p10230[4] or p10235.4.
Description:
Sets the sign for the test torque for the safe brake test.
This parameter is only valid for "SBT for test stop selection" (p10203 = 2).
Value:
0:
Positive
1:
Negative
Dependency:
Refer to: p10203
Description:
Sets the factor for the test torque of sequence 2 for the safe brake test.
The factor is referred to the holding torque of the brake (p10209).
Index:
[0] = Brake 1
[1] = Brake 2
Dependency:
Refer to: p10209, p10230, p10235
Note:
The test sequence is selected using p10230[4] or p10235.4.
Description:
Sets the test duration for sequence 2 for the safe brake test.
The test torque is available for this time at the closed brake.
Index:
[0] = Brake 1
[1] = Brake 2
Dependency:
Refer to: p10230, p10235
Note:
The test sequence is selected using p10230[4] or p10235.4.
The set time is rounded internally to an integer multiple of the monitoring clock cycle.
Description:
Sets the tolerated position deviation for sequence 2 for the safe brake test.
Index:
[0] = Brake 1
[1] = Brake 2
p10218
SI Motion SBT test torque sign / SBT M_test sign
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
2837
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p10220[0...1]
SI Motion SBT test torque factor sequence 2 / SBT M_test fact 2
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2836
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.30 1.00
1.00
p10221[0...1]
SI Motion SBT test duration sequence 2 / SBT t_test seq 2
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2836
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
20 [ms]
10000 [ms]
1000 [ms]
p10222[0...1]
SI Motion SBT position tolerance sequence 2 / SBT pos_tol seq 2
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2836
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.001 [mm]
360.000 [mm]
1.000 [mm]
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......