4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1376
List Manual (LH2), 07/2016, A5E03263479A
F01031
Sign-of-life failure for OFF in REMOTE
Message value:
-
Message class:
Communication error to the higher-level control system (9)
Drive object:
B_INF, VECTOR_G
Component:
None
Propagation:
GLOBAL
Reaction:
Vector: OFF3 (IASC/DCBRK, NONE, OFF1, OFF2, STOP2)
Infeed: OFF1 (NONE, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
With the "OFF in REMOTE" mode active, no sign-of-life was received within 3 seconds.
Remedy:
- check the data cable connection at the serial interface for the Control Unit (CU) and operator panel.
- check the data cable between the Control Unit and operator panel.
A01032 (F)
ACX: all parameters must be saved
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
All objects
Component:
Control Unit (CU)
Propagation:
LOCAL
Reaction:
NONE
Acknowledge:
NONE
Cause:
The parameters of an individual drive object were saved (p0971 = 1), although there is still no backup of all drive
system parameters.
The saved object-specific parameters are not loaded the next time that the system powers up.
For the system to successfully power up, all of the parameters must have been completely backed up.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
See also: p0971 (Save drive object parameters)
Remedy:
Save all parameters (p0977 = 1 or "copy RAM to ROM").
See also: p0977 (Save all parameters)
Reaction upon F:
Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F:
IMMEDIATELY
F01033
Units changeover: Reference parameter value invalid
Message value:
Parameter: %1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, ENC, VECTOR_G
Component:
None
Propagation:
GLOBAL
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
When changing over the units to the referred representation type, it is not permissible for any of the required
reference parameters to be equal to 0.0
Fault value (r0949, parameter):
Reference parameter whose value is 0.0.
See also: p0349 (System of units motor equivalent circuit diagram data), p0505 (Selecting the system of units),
p0595 (Technological unit selection)
Remedy:
Set the value of the reference parameter to a number different than 0.0.
See also: p0304, p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......