Function diagram
8
7
6
5
4
3
2
1
fp_9627_51_eng.vsd
SINAMICS
25.04.16 V04.08.00
Terminal Module 150 (TM150) - Temperature evaluation 2x2 wire (channels 0 11)
DO: TM150
X53x.3
X53x.4
x = 1, 2,
3, 4, 5, 6
Sensor R
r4101[6...11]
1650 (PTC)
100 (Bimetal)
KTY84
PTC/
Bimetal
NC
contact
Sensor type
p4100[6...11]
<2>
A
D
Calculate
resistance
0
1
R
T
250 °C
-99 °C
KTY84
PTC
-50 °C
250 °C
1
0
Bimetal
-300 °C
6
5
4
2
1
0
PT100
PT1000
PT100
R
T
250 °C
-99 °C
PT1000
R
T
250 °C
-99 °C
50/60 Hz
Cable R value
p4110[6...11]
+
Save cable
resistance
r4104.12
"Channel y alarm is present"
A35926 A35931
"Error temperature sensor channel y"
(y = 6 11)
r4105[6...11]
Temp act value
Alarm is present
-300 °C
1
Alarm threshold
-99...251 [°C]
p4102[12, 14, 16, 18, 20, 22] (251)
Fault threshold
-99...251 [°C]
p4102[13, 15, 17, 19, 21, 23] (251)
<1>
1
0
only for
KTY84, PT100,
PT1000
Group formation
p4118[6...11] (5)
r4104.14
r4104.16
r4104.18
r4104.20
r4104.22
r4104.13
"Channel y fault is present"
r4104.15
r4104.17
r4104.19
r4104.21
r4104.23
0
1
0
1
[9625.6]
p4108[0...5] = 1
X53x.1
X53x.2
A
D
Temperature evaluation
Channel 0
Channel 5
[9626]
<1> For p4102[0...23] = 251 °C the evaluation of the appropriate threshold is deactivated.
<2> p4100[0...11]
= 0: Evaluation deactivated
= 1: PTC thermistor (with monitoring for short-circuit)
= 2: KTY84 (with monitoring for wire break and short-circuit)
= 4: Bimetal NC contact (no monitoring)
= 5: PT100 (with monitoring for wire break and short-circuit)
= 6: PT1000 (with monitoring for wire break and short-circuit)
<3> For p4103 = 0 s and sensor type "KTY84", "PT100", "PT1000" (p4100[0...11] = 2, 5, 6) the following applies:
- The relevant fault can only be triggered via the fault threshold (the timer output is always logical 0).
For p4103 = 0 s and sensor type "PTC thermistor", "Bimetal NC contact" (p4100[0...11] = 1, 4) the following applies:
- The corresponding alarm and fault are output simultaneously (delay time = 0 s).
Measuring
method
0: 1x2 wire
1: 2x2 wire
2: 3 wire
3: 4 wire
Measuring
method
0: 1x2 wire
1: 2x2 wire
2: 3 wire
3: 4 wire
[9625]
Temperature evaluation
Channel 6
Channel 11
<1>
Determine cable resistance
(with short-circuited sensor)
F35407 (Channel 11)
F35406 (Channel 10)
F35405 (Channel 9)
F35404 (Channel 8)
F35403 (Channel 7)
F35402 (Channel 6)
A35417 (Channel 11)
A35416 (Channel 10)
A35415 (Channel 9)
A35414 (Channel 8)
A35413 (Channel 7)
A35412 (Channel 6)
Temperature actual value
T
0
0.0...600.0 [s]
p4103[6...11] (0.0)
<3>
p4121 (0)
Filt f_line
26000.00 μs)
R_Leit Mes
p4109[6...11]
p4119[6...11]
1
0
p4122[6...11]
TM150 T
Temp_filt T
r4120[6...11]
Number of
active channels · 100 ms
MAX
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......