2 Parameters
2.2 List of parameters
SINAMICS G130/G150
544
List Manual (LH2), 07/2016, A5E03263479A
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Alarm buffer structure (general principle):
r2122[0], r2124[0], r2123[0], r2125[0] --> alarm 1 (the oldest)
. . .
r2122[7], r2124[7], r2123[7], r2125[7] --> Alarm 8 (the latest)
When the alarm buffer is full, the alarms that have gone are entered into the alarm history:
r2122[8], r2124[8], r2123[8], r2125[8] --> Alarm 1 (the latest)
. . .
r2122[63], r2124[63], r2123[63], r2125[63] --> alarm 56 (the oldest)
Description:
Displays the system runtime in milliseconds when the alarm occurred.
Dependency:
Refer to: r2110, r2114, r2122, r2124, r2125, r2134, r2145, r2146, r3121, r3123
Notice:
The time comprises r2145 (days) and r2123 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
Description:
Displays additional information about the active alarm (as integer number).
Dependency:
Refer to: r2110, r2122, r2123, r2125, r2134, r2145, r2146, r3121, r3123
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
Description:
Displays the system runtime in milliseconds when the alarm was cleared.
Dependency:
Refer to: r2110, r2114, r2122, r2123, r2124, r2134, r2145, r2146, r3121, r3123
Notice:
The time comprises r2146 (days) and r2125 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
r2123[0...63]
Alarm time received in milliseconds / t_alarm recv ms
All objects
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
8050, 8065
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- [ms]
- [ms]
- [ms]
r2124[0...63]
Alarm value / Alarm value
All objects
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Integer32
Dyn. index:
-
Func. diagram:
8050, 8065
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
r2125[0...63]
Alarm time removed in milliseconds / t_alarm res ms
All objects
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
8050, 8065
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- [ms]
- [ms]
- [ms]
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......