SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
167
2 Parameters
2.2 List of parameters
Description:
Setting to invert actual values.
Note:
The inversion influences the following parameters:
Bit 00: r0061, r0063 (exception: encoderless control), r0094
Bit 01: r0482, r0483
Description:
Setting to invert actual values.
Note:
The inversion influences the following parameters:
Bit 00: r0061, r0063 (exception: encoderless control), r0094
Bit 01: r0482, r0483
Description:
Sets the configuration for position tracking of a measuring gear.
Notice:
For p0411.3 = 1 the following applies:
If position tracking is activated for incremental encoders, only the position actual value is stored. Axis or encoder
motion is not detected when deactivated! Any tolerance window entered in p0413 has no effect.
p0410[0...n]
Encoder inversion actual value / Enc inv act value
VECTOR_G, ENC
Can be changed:
C2(4)
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
EDS, p0140
Func. diagram:
4704, 4710,
4711, 4715
P-Group:
Encoder
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Invert speed actual value
Yes
No
4710,
4711,
4715
01
Invert position actual value
Yes
No
4704
p0410[0...n]
Encoder inversion actual value / Enc inv act value
ENC (Lin_enc)
Can be changed:
C2(4)
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
EDS, p0140
Func. diagram:
4704, 4710,
4711, 4715
P-Group:
Encoder
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Invert velocity actual value
Yes
No
4710,
4711,
4715
01
Invert position actual value
Yes
No
4704
p0411[0...n]
Measuring gear configuration / Meas gear config
VECTOR_G, ENC
Can be changed:
C2(4)
Calculated:
-
Access level:
1
Data type:
Unsigned32
Dyn. index:
EDS, p0140
Func. diagram:
4704
P-Group:
Encoder
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Measuring gear activate position tracking
Yes
No
-
01
Axis type
Linear axis
Rotary axis
-
02
Measuring gear reset position
Yes
No
-
03
Meas. gearbox, activate pos. tracking for
incremental encoders
Yes
No
-
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......