SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
385
2 Parameters
2.2 List of parameters
Note:
For bit 01:
When the bit is set, the I component of the speed controller is kept when changing into the open-loop controlled
mode.
For bit 16:
When the bit is set, the integral component of the speed controller is only held if it reaches the torque limit.
For bit 19:
When this bit is set, speed overshoots when accelerating along the torque limit and for load surges are reduced. If
the setpoint torque reaches the torque limit, then the integral component is set to the difference between the torque
limit and P component.
For bits 20, 23:
The acceleration model for the speed setpoint is only active if p1496 is not zero. When the acceleration model and
the ramp-function generator (p1145) are simultaneously activated, it is recommended that p1400 bit 16 is set (this
allows the I component to run freely up to the torque limit).
For bit 24:
When the bit is set, assuming that the motor accelerates smoothly, the moment of inertia can be determined faster.
For bit 25:
When the bit is set, for high dynamic starting in the I/f mode, the acceleration precontrol torque smoothing only has a
short minimum time (4 ms).
Description:
Sets the configuration for flux setpoint control
Note:
For bit 00 (only for induction motors):
Initially, the flux is only established with a low rate of rise when magnetizing the induction motor. The flux setpoint
p1570 is reached again at the end of the magnetizing time p0346.
22
Obtain moment of inertia estimator value for
pulse inhibit
Yes
No
6030
23
Acceleration model (with speed encoder)
Yes
No
6030
24
Accelerated moment of inertia estimator
active
Yes
No
6030
25
Acceleration torque instantaneous in the I/f
mode
Yes
No
-
p1401[0...n]
Flux control configuration / Flux ctrl config
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
DDS, p0180
Func. diagram:
6491
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-
-
0000 0000 0000 1110 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Flux setpoint soft starting active
Yes
No
6722,
6725
01
Flux setpoint differentiation active
Yes
No
6723,
6726
02
Flux build-up control active
Yes
No
6722,
6723,
6725,
6726
03
Flux characteristic load-dependent
Yes
No
6725
04
Flux controller (ASM with encoder)
Yes
No
-
05
Flux impression (ASM with encoder)
with model chngov
From 30 % n_rated
-
06
Quick magnetizing
Yes
No
6722
07
Pre-control speed limitation
Yes
No
6640
08
Speed limiting controller
With M_limits
With I_limits
6640
09
Dynamic load-dependent flux boost
Yes
No
6790,
6823
10
Flux boost low speed
Yes
No
6790,
6823
13
Precontrol characteristic (PESM)
Yes
No
-
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......