SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
467
2 Parameters
2.2 List of parameters
Description:
Setting to change the direction of rotation.
If the parameter is changed, it reverses the direction of rotation of the motor and the encoder actual value without
changing the setpoint.
Value:
0:
CW
1:
CCW
Dependency:
Refer to: F07434
Danger:
When using external speed actual values for the speed controller (see p1440), for a direction of rotation change
(p1821 = 1), then its polarity must also be changed (e.g. for drive object ENCODER via p0410). Otherwise, a positive
coupling can occur in the speed control loop and the drive would then be accelerated up to the speed limit.
Caution:
For 12-pulse converters with 30° offset angle for system 2, for a direction of rotation reversal, the phase offset
changes by 60° as the sign of the angle offset changes. This can be adapted in p1810.15.
Changing the direction using p1820 or p1821 is not recognized by the "Safe Direction without encoder". As a
consequence, the limit provided by SDI (Safe Direction) from r9733 no longer functions.
Notice:
An appropriate fault is output for a drive data set changeover where the direction of rotation changes and the pulses
are enabled.
Note:
For operation with the phase sequence U/V/W, the direction of rotation is defined when viewing the face side of the
motor output shaft.
When changing the direction of rotation, the rotating field direction of the current controller is reversed. The speed
actual value (e.g. r0063) is also reversed so that the control sense is kept and internally causing the direction of
rotation to be reversed with the same setpoint. Further, the position actual values of the actual encoder are reversed
(e.g. r0482[0...2]).
p1820 can be used to reverse the direction of the motor without reversing the encoder actual value.
Description:
Sets the tolerance time for line phase monitoring for blocksize power units.
If a line phase fault is present for longer than this tolerance time, then a corresponding fault is output.
Dependency:
Refer to: F30011
Notice:
When operating with a failed line phase, depending on the active power, values higher than the default value can
either immediately damage the power unit or damage it over the long term.
Note:
For the setting p1822 = maximum value, line phase monitoring is deactivated.
Description:
Sets the threshold voltage drop of the valves (power semiconductor devices) to be compensated.
Note:
The value is automatically calculated in the motor data identification routine.
p1821[0...n]
Dir of rot / Dir of rot
VECTOR_G
Can be changed:
C2(3)
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
DDS, p0180
Func. diagram:
4704, 4710,
4711, 4715, 5730, 6730, 6731,
6732
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p1822
Power unit line phases monitoring tolerance time / PU ph monit t_tol
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
4
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
500 [ms]
540000 [ms]
1000 [ms]
p1825
Converter valve threshold voltage / Threshold voltage
VECTOR_G
Can be changed:
U, T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Modulation
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 [Vrms]
100.0 [Vrms]
0.6 [Vrms]
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......