List Manual (LH2), 07/2016, A5E03263479A
405
2 Parameters
2.2 List of parameters
Description:
Displays the torque setpoint before entering the supplementary torque.
For closed-loop speed control, r1508 corresponds to the speed controller output; for closed-loop torque control,
r1508 corresponds to the torque setpoint of the signal source assigned in p1503.
Description:
Sets the signal source for supplementary torque 1.
Description:
Sets the signal source for scaling the supplementary torque 1.
Description:
Sets the signal source for supplementary torque 2.
Description:
Sets the scaling for supplementary torque 2.
r1508
CO: Torque setpoint before supplementary torque / M_set bef. M_suppl
VECTOR_G (n/M)
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
6030, 6060,
6722
P-Group:
Closed-loop control
Unit group:
7_1
Unit selection:
p0505
Not for motor type:
REL
Scaling:
p2003
Expert list:
1
Min Max
Factory
setting
- [Nm]
- [Nm]
- [Nm]
p1511[0...n]
CI: Supplementary torque 1 / M_suppl 1
VECTOR_G (n/M)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
6020, 6060
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
p2003
Expert list:
1
Min Max
Factory
setting
- -
0
p1512[0...n]
CI: Supplementary torque 1 scaling / M_suppl 1 scal
VECTOR_G (n/M)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
5060, 6060
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
0
p1513[0...n]
CI: Supplementary torque 2 / M_suppl 2
VECTOR_G (n/M)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
6020, 6060
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
p2003
Expert list:
1
Min Max
Factory
setting
- -
0
p1514[0...n]
Supplementary torque 2 scaling / M_suppl 2 scal
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6020, 6060
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
-2000.0 [%]
2000.0 [%]
100.0 [%]
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......