SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
671
2 Parameters
2.2 List of parameters
Description:
Sets the fault threshold/alarm threshold for Terminal Module 31 (TM31).
A35211 is initiated, if the temperature actual value r4105[0] > p4102[0]
F35207 is initiated if the temperature actual value r4105[0] > p4102[1] or timer p4103[0] has expired
For alarm A35211 the following applies:
- Remains until the temperature actual value (r4105) reaches or falls below the value (p4102[0] - hysteresis).
For fault F35207 the following applies:
- Remains until the temperature actual value (r4105) reaches or falls below the value (p4102[1] - hysteresis) and the
fault has been acknowledged.
- the hysteresis value is 5 K and cannot be changed by the user.
Index:
[0] = Alarm threshold
[1] = Fault threshold
Dependency:
Refer to: r4104
Notice:
Fault F35207 only causes the drive to be shut down if there is at least one BICO interconnection between the drive
and TM31.
For p4102[0...1] = 251 °C, evaluation of the corresponding threshold is deactivated.
For sensor type "PTC thermistor" (p4100 = 1), the following applies:
To activate the alarm or fault, p4102[0...1] must be set <= 250 °C.
Description:
Sets the delay time for the output of the fault for the temperature evaluation of Terminal Module 120 (TM120).
The timer is started when the alarm threshold (p4102[0, 2, 4, 6]) is exceeded.
If the delay time has expired and the alarm threshold has, in the meantime, not been fallen below, then fault F35207
... F53210 is output.
The fault can be acknowledged, if, after the delay time has expired, the alarm threshold is again fallen below.
For sensor type "KTY84" "PT1000" (p4100[0...3] = 2, 6), the following applies:
If the fault threshold (p4102[1, 3, 5, 7]) is exceeded before the delay time has expired, then fault F35207 ... F35210 is
immediately output.
For sensor type "PTC thermistor" (p4100[0...3] = 1), the following applies:
- Alarm and fault threshold simultaneously respond. The fault is only issued after the delay time has expired.
Index:
[0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
Dependency:
Refer to: r4104
Warning:
Fault F35207 ... F35210 only causes the drive to shut down if there is at least one BICO interconnection between the
drive and TM120.
Note:
With p4103 = 0 ms, the timer is deactivated and only the fault threshold is effective.
p4102[0...1]
TM31 fault threshold/alarm threshold / TM31 F/A_thresh
TM31
Can be changed:
U, T
Calculated:
-
Access level:
1
Data type:
Integer16
Dyn. index:
-
Func. diagram:
9576
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-48 [°C]
251 [°C]
[0] 100 [°C]
[1] 120 [°C]
p4103[0...3]
TM120 temperature evaluation delay time / TM120 temp t_delay
TM120
Can be changed:
U, T
Calculated:
-
Access level:
1
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
9605, 9606
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [ms]
600000.000 [ms]
0.000 [ms]
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......