SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
253
2 Parameters
2.2 List of parameters
Description:
Sets the ohmic excitation resistance of the main exciter machine for brushless excitation.
When the rotor resistance is known, this value can be added to the excitation resistance.
Notice:
For a value = 0, brushless excitation is not activated.
Note:
BLE: brushless excitation
Description:
Runs the corresponding macro files.
The binector inputs of the corresponding command data set are appropriately interconnected.
The selected macro file must be available on the memory card/device memory.
Example:
p0700 = 6 --> macro file PM000006.ACX is run.
Dependency:
Refer to: p0015, p1000, p1500, r8571
Notice:
No errors were issued during quick commissioning (p3900 = 1) when writing to parameters of the QUICK_IBN group!
When executing a specific macro, the corresponding programmed settings are made and become active.
Note:
The macros in the specified directory are displayed in r8571. r8571 is not in the expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
BI: Binector Input
CDS: Command Data Set
Description:
Runs the corresponding macro files.
The selected macro file must be available on the memory card/device memory.
Example:
p0700 = 6 --> macro file PM000006.ACX is run.
Dependency:
Refer to: r8571
Notice:
No errors were issued during quick commissioning (p3900 = 1) when writing to parameters of the QUICK_IBN group!
When executing a specific macro, the corresponding programmed settings are made and become active.
Note:
The macros in the specified directory are displayed in r8571. r8571 is not in the expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
BI: Binector Input
CDS: Command Data Set
p0698[0...n]
Brushless excitation excitation resistance / BLE exc_resist
VECTOR_G (n/M)
Can be changed:
C2(3), U, T
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
MDS, p0130
Func. diagram:
6727
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
ASM, PMSM, REL,
RESM
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-10.00000 [ohm]
10.00000 [ohm]
0.00000 [ohm]
p0700[0...n]
Macro Binector Input (BI) / Macro BI
VECTOR_G, B_INF
Can be changed:
C2(1), T
Calculated:
-
Access level:
1
Data type:
Unsigned32
Dyn. index:
CDS, p0170
Func. diagram:
-
P-Group:
Commands
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 999999
0
p0700
Macro Binector Input (BI) for TMs / Macro BI TM
TM31, TB30
Can be changed:
C2(1), T
Calculated:
-
Access level:
1
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
Commands
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 999999
0
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......