4 Faults and alarms
4.2 List of faults and alarms
F07562 (A)
Drive, encoder: Position tracking, incremental encoder not possible
Message value:
Fault cause: %1, component number: %2, encoder data set: %3
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, ENC, VECTOR_G
Component:
None
Propagation:
GLOBAL
Reaction:
Vector: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Infeed: OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The requested position tracking for incremental encoders is not supported.
Fault value (r0949, interpret hexadecimal):
ccccbbaa hex
aa = encoder data set
bb = component number
cccc = fault cause
cccc = 00 hex = 0 dec
The encoder type does not support the "Position tracking incremental encoder" function.
cccc = 01 hex = 1 dec
Position tracking cannot be activated because the memory of the internal NVRAM is not sufficient or a Control Unit
does not have an NVRAM.
cccc = 04 hex = 4 dec
A linear encoder is used that does not support the "position tracking" function.
See also: p0404 (Encoder configuration effective), p0411 (Measuring gear configuration), r0456 (Encoder
configuration supported)
Remedy:
- check the encoder parameterization (p0400, p0404).
- use a Control Unit with sufficient NVRAM.
- if required, de-select position tracking for the incremental encoder (p0411.3 = 0).
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F07563 (A)
Drive encoder: XIST1_ERW configuration incorrect
Message value:
Fault cause: %1, encoder data set: %2
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, ENC, VECTOR_G
Component:
None
Propagation:
GLOBAL
Reaction:
Vector: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Infeed: OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
An incorrect configuration was identified for the "Absolute position for incremental encoder" function.
Fault value (r0949, interpret decimal):
Fault cause:
1 (= 01 hex):
The "Absolute value for incremental encoder" function is not supported (r0459.13 = 0).
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
yyxx dec: yy = fault cause, xx = encoder data set
See also: r0459 (Sensor Module properties extended), p4652 (XIST1_ERW reset mode)
Remedy:
For fault value = 1:
- upgrade the Sensor Module firmware version.
- check the mode (p4652 = 1, 3 requires the property r0459.13 = 1).
Reaction upon A:
NONE
Acknowl. upon A:
NONE
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......