2 Parameters
2.2 List of parameters
SINAMICS G130/G150
842
List Manual (LH2), 07/2016, A5E03263479A
Description:
Displays the PROFIdrive PZD state.
Dependency:
Refer to: p2044
Note:
When using the "setpoint failure" signal, the bus can be monitored and an application-specific response triggered
when the setpoint fails.
Description:
Sets the delay time to initiate fault F01910 after a setpoint failure.
The time until the fault is initiated can be used by the application. This means that is is possible to respond to the
failure while the drive is still operational (e.g. emergency retraction).
Dependency:
Refer to: r2043
Description:
Sets the sampling time for the cyclic interface 2 (IF2).
Note:
The system only permits certain sampling times and after writing to this parameter, displays the value that has
actually been set.
For clock cycle synchronous operation, the specified bus cycle time applies (Tdp).
Description:
Displays the receive configuration data for the COMM BOARD.
r8843.0...2
BO: IF2 PZD state / IF2 PZD state
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned8
Dyn. index:
-
Func. diagram:
2410
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Setpoint failure
Yes
No
-
01
Clock cycle synchronous operation active
Yes
No
-
02
Fieldbus oper
Yes
No
-
p8844
IF2 fault delay / IF2 F delay
VECTOR_G, B_INF,
ENC
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2410
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [s]
100 [s]
0 [s]
p8848
IF2 PZD sampling time / IF2 PZD t_sample
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
C1(3)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1.00 [ms]
16.00 [ms]
4.00 [ms]
r8849[0...139]
COMM BOARD receive configuration data / CB r config_dat
CU_G130_PN (COMM
BOARD, PN CBE20),
CU_G150_PN (COMM
BOARD, PN CBE20),
CU_G130_DP (COMM
BOARD, PN CBE20),
CU_G150_DP (COMM
BOARD, PN CBE20)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......