2 Parameters
2.2 List of parameters
SINAMICS G130/G150
92
List Manual (LH2), 07/2016, A5E03263479A
Description:
Setting to activate/deactivate a power unit component.
Value:
0:
Deactivate component
1:
Activate component
2:
Component deactivate and not present
Recommendation:
After inserting a component, before activating, first wait for Alarm A01317.
Dependency:
Refer to: r0126
Refer to: A01314, A01317
Caution:
For a parallel connection, the following applies:
When deactivating individual power units using this parameter, it is not permissible that the power units of the parallel
connection involved are connected. Infeed units should be disconnected from the line supply (for example, using a
contactor). Motor feeder cables should be disconnected. In addition, defective power units should be disconnected
from the DC link.
Notice:
It is not permissible to deactivate drive objects with safety functions enabled.
Note:
The activation of a component can be rejected if the component was inserted for the first time. In this case, it is only
possible to activate the component when the pulses for all of the drive objects are inhibited.
For units connected in parallel, when one of the power units is deactivated, then the enable in p7001 is withdrawn.
For value = 0, 2:
When a component is deactivated it no longer outputs any errors.
If value = 0:
The component was completely commissioned and is deactivated using this value. It can be removed from the
DRIVE-CLiQ without any error.
If value = 1:
The component must be available for error-free operation.
If value = 2:
A component in a project generated offline and set to this value must never be inserted in the actual topology from
the very start. This means that the component is marked to be bypassed in the DRIVE-CLiQ line.
For components that comprise several individual components (e.g. Double Motor Modules), it is not permissible to
set just one subset to this value.
Description:
Displays the "active/inactive" state of a power unit component.
Value:
0:
Component inactive
1:
Component active
Dependency:
Refer to: p0105, p0125, p0897
p0125[0...n]
Activate/deactivate power unit components / PU_comp act/deact
VECTOR_G, B_INF
Can be changed:
C1(4), T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
PDS, p0120
Func. diagram:
-
P-Group:
Data sets
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 2
1
r0126[0...n]
Power unit components active/inactive / PU comp act/inact
VECTOR_G, B_INF
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
PDS, p0120
Func. diagram:
-
P-Group:
Data sets
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
-
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......