2 Parameters
2.2 List of parameters
SINAMICS G120D
362
List Manual (LH14), 01/2016, A5E33842313
Description:
Sets a block number.
-1: Invalid block number. These blocks are not taken into account.
0 ... 15: valid block number.
Dependency:
The number of indices depends on p2615.
Refer to: p2615, p2617, p2618, p2619, p2620, p2621, p2622, p2623, p2624
Description:
Sets the target position for the traversing block.
Dependency:
The number of indices depends on p2615.
Refer to: p2615, p2616, p2618, p2619, p2620, p2621, p2622, p2623, p2624
Note:
The target position is approached in either relative or absolute terms depending on p2623.
Description:
Sets the velocity for the traversing block.
Dependency:
The number of indices depends on p2615.
Refer to: p2615, p2616, p2617, p2619, p2620, p2621, p2622, p2623, p2624, p2646
Note:
The velocity can be influenced using the velocity override (p2646).
Description:
Sets the acceleration override for the traversing block.
The override refers to the maximum acceleration (p2572).
Dependency:
The number of indices depends on p2615.
Refer to: p2572, p2615, p2616, p2617, p2618, p2620, p2621, p2622, p2623, p2624
p2616[0...n]
EPOS traversing block block number / Trav_blk, blkNo.
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
U, T
Scaling:
-
Dyn. index:
p2615
Unit group:
-
Unit selection:
-
Func. diagram:
3616
Min Max
Factory
setting
-1 15
-1
p2617[0...n]
EPOS traversing block position / Trav_block pos
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
1
Calculated:
-
Data type:
Integer32
Can be changed:
U, T
Scaling:
-
Dyn. index:
p2615
Unit group:
-
Unit selection:
-
Func. diagram:
3616
Min Max
Factory
setting
-2147482648 [LU]
2147482647 [LU]
0 [LU]
p2618[0...n]
EPOS traversing block velocity / Trav_block v
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
1
Calculated:
-
Data type:
Integer32
Can be changed:
U, T
Scaling:
-
Dyn. index:
p2615
Unit group:
-
Unit selection:
-
Func. diagram:
3616
Min Max
Factory
setting
1 [1000 LU/min]
40000000 [1000 LU/min]
600 [1000 LU/min]
p2619[0...n]
EPOS traversing block acceleration override / Trav_block a_over
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
1
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
p2615
Unit group:
-
Unit selection:
-
Func. diagram:
3616
Min Max
Factory
setting
1.0 [%]
100.0 [%]
100.0 [%]
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......