2 Parameters
2.2 List of parameters
SINAMICS G120D
248
List Manual (LH14), 01/2016, A5E33842313
Description:
Sets the integral time for the Lh adaptation of the motor model for an induction motor (ASM).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Description:
Displays the corrective value for the Lh adaptation of the motor model for an induction motor (ASM).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Refer to: p0826, p1780
Note:
The adaptation result is reset if the magnetizing inductance of the induction motor is changed (p0360, r0382). This
also happens when changing over the data set if a different motor is not being used (p0826).
The display of the inactive data sets is only updated when changing over the data set.
Description:
Displays the switch-on stator frequency/ primary section frequency for the Lh adaptation for the induction motor
(ASM).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Description:
Displays the switch-on slip frequency for the Lh adaptation for the induction motor (ASM).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Description:
Sets the integral time of the kT adaptation of the motor model for a permanent-magnet synchronous motor (PMSM).
p1786[0...n]
Motor model Lh adaptation integral time / MotMod Lh Tn
Access level:
4
Calculated:
p0340 = 1,3,4
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
10 [ms]
10000 [ms]
100 [ms]
r1787[0...n]
Motor model Lh adaptation corrective value / MotMod Lh corr
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [mH]
- [mH]
- [mH]
r1791
Motor model Lh adaptation switch-on frequency / MotMod Lh f_on
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [Hz]
- [Hz]
- [Hz]
r1792
Motor model Lh adaptation switch-on slip / MotMod Lh fslip
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [Hz]
- [Hz]
- [Hz]
p1795[0...n]
Motor model kT adaptation integral time / MotMod kT Tn
Access level:
4
Calculated:
p0340 = 1,3,4
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6731
Min Max
Factory
setting
10 [ms]
10000 [ms]
100 [ms]
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......