2 Parameters
2.2 List of parameters
SINAMICS G120D
560
List Manual (LH14), 01/2016, A5E33842313
Description:
Setting parameter for the run sequence of instance PLI 1 within the run-time group set in p20382.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description:
Sets the telegram number for PROFIsafe.
Value:
0:
No PROFIsafe telegram selected
30:
PROFIsafe standard telegram 30, PZD-1/1
900:
PROFIsafe SIEMENS telegram 900, PZD-2/2
998:
Compatibility mode (as for firmware version < 4.6)
Note:
For p9601.3 = p9801.3 = 1 (PROFIsafe enabled), the following variants exist when parameterizing PROFIsafe
telegram 30:
- p9611 = p9811 = 998 and p60022 = 0
- p9611 = p9811 = 998 and p60022 = 30
- p9611 = p9811 = 30 and p60022 = 30
Description:
Sets the telegram number for PROFIsafe.
Value:
0:
No PROFIsafe telegram selected
30:
PROFIsafe standard telegram 30, PZD-1/1
998:
Compatibility mode (as for firmware version < 4.6)
Note:
For p9601.3 = p9801.3 = 1 (PROFIsafe enabled), the following variants exist when parameterizing PROFIsafe
telegram 30:
- p9611 = p9811 = 998 and p60022 = 0
- p9611 = p9811 = 998 and p60022 = 30
- p9611 = p9811 = 30 and p60022 = 30
Description:
Sets the telegram for the Safety Info Channel (SIC).
The SIC telegram p60122 is attached directly to the PZD telegram p0922/p2079.
Value:
700:
Supplementary telegram 700, PZD-0/3
999:
Free telegram configuration with BICO
Dependency:
Refer to: p0922, p2071, p2079
p20383
PLI 1 run sequence / PLI 1 RunSeq
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7226
Min Max
Factory
setting
0 32000
990
p60022
PROFIsafe telegram selection / Ps telegram_sel
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 998
998
p60022
PROFIsafe telegram selection / Ps telegram_sel
CU240D-2_DP
CU240D-2_PN
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 998
998
p60122
PROFIdrive SIC telegram selection / Pd SIC telegr
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2423
Min Max
Factory
setting
700 999 999
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......