2 Parameters
2.2 List of parameters
SINAMICS G120D
478
List Manual (LH14), 01/2016, A5E33842313
Dependency:
Refer to: r9772
Note:
For bit 00:
When STO is selected, the cause is displayed in bits 16 ... 21.
For bit 18:
When the bit is set, STO is selected via PROFIsafe.
Description:
Displays the Safety Integrated status on processor 2.
Dependency:
Refer to: r9772
Note:
For bit 00:
When STO is selected, the cause is displayed in bits 16 ... 21.
For bit 18:
When the bit is set, STO is selected via PROFIsafe.
Description:
Displays the checksum for the Safety Integrated parameters checked using checksums on processor 2 (actual
checksum).
Dependency:
Refer to: r9798, p9899
07
STO terminal state on processor 2 (Basic
Functions)
High
Low
-
09
STOP A cannot be acknowledged active
Yes
No
2802
10
STOP A active
Yes
No
2802
15
STOP F active
Yes
No
2802
16
STO cause: Safety comm. mode
Yes
No
-
17
STO cause selection via terminal (Basic
Functions)
Yes
No
-
18
STO cause: Selection via motion monitoring
functions
Yes
No
-
20
STO cause selection PROFIsafe (Basic
Functions)
Yes
No
-
21
STO cause selection on the other
monitoring channel
Yes
No
-
r9872.0...21
CO/BO: SI status (processor 2) / SI Status P2
CU240D-2_DP
CU240D-2_PN
Access level:
2
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2804
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
STO selected on processor 2
Yes
No
2810
01
STO active on processor 2
Yes
No
2810
07
STO terminal state on processor 2 (Basic
Functions)
High
Low
-
09
STOP A cannot be acknowledged active
Yes
No
2802
10
STOP A active
Yes
No
2802
15
STOP F active
Yes
No
2802
16
STO cause: Safety comm. mode
Yes
No
-
17
STO cause selection via terminal (Basic
Functions)
Yes
No
-
20
STO cause selection PROFIsafe (Basic
Functions)
Yes
No
-
21
STO cause selection on the other
monitoring channel
Yes
No
-
r9898
SI actual checksum SI parameters (processor 2) / SI act_chksm P2
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2800
Min Max
Factory
setting
- - -
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......