SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
257
2 Parameters
2.2 List of parameters
24:
Rectangular voltage vector input with filter
25:
Triangular voltage vector input with filter
26:
Enter voltage vector with DTC correction
27:
Enter voltage vector with AVC
28:
Enter voltage vector with DTC + AVC correction
Dependency:
"Quick commissioning" must be carried out (p0010 = 1, p3900 > 0) before executing the motor data identification
routine!
When selecting the motor data identification routine, the drive data set changeover is suppressed.
Refer to: p1900
Refer to: F07990, A07991
Notice:
After the motor data identification (p1910 > 0) has been selected, alarm A07991 is output and a motor data
identification routine is carried out as follows at the next switch-on command:
- current flows through the motor and a voltage is present at the drive converter output terminals.
- during the identification routine, the motor shaft can rotate through a maximum of half a revolution.
- however, no torque torque is generated.
Note:
If there is a motor holding brake, it must be open (p1215 = 2).
To permanently accept the determined settings they must be saved in a non-volatile fashion (p0971).
When setting p1910, the following should be observed:
1. "With acceptance" means:
The parameters specified in the description are overwritten with the identified values and therefore have an influence
on the controller setting.
2. "Without acceptance" means:
The identified parameters are only displayed in the range r1912 ... r1926 (service parameters). The controller
settings remain unchanged.
3. For settings 27 and 28, the AVC configuration set using p1840 is active.
The switch-on command must remain set during a measurement and after the measurement has been completed,
the drive automatically resets it. The duration of the measurements can lie between 0.3 s and several minutes. This
time is mainly influenced by the motor size. At the end of the motor data identification, p1910 is automatically set to 0,
if only the stationary measurement is selected, then p1900 is also reset to 0, otherwise, the rotating measurement is
activated.
Description:
Sets the motor data identification routine.
The motor data identification routine is carried out after the next switch-on command.
p1910 = 1:
All motor data and the drive converter characteristics are identified and then transferred to the following parameters:
p0350, p0354, p0356, p0357, p0358, p0360, p1825, p1828, p1829, p1830
After this, the control parameter p0340 = 3 is automatically calculated.
p1910 = 20:
Only for internal SIEMENS use.
Value:
0:
Inhibited
1:
Complete identification (ID) and acceptance of motor data
2:
Complete identification (ID) of motor data without acceptance
20:
Voltage vector input
21:
Voltage vector input without filter
22:
Rectangular voltage vector input without filter
23:
Triangular voltage vector input without filter
24:
Rectangular voltage vector input with filter
25:
Triangular voltage vector input with filter
26:
Enter voltage vector with DTC correction
27:
Enter voltage vector with AVC
28:
Enter voltage vector with DTC + AVC correction
p1910
Motor data identification selection / MotID selection
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 28
1
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......