SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
107
2 Parameters
2.2 List of parameters
Description:
Displays the time between the last two BERO pulses.
The measuring time is specified as 32-bit value with a resolution of 1/48 µs.
If a new pulse is not received before the maximum measured time in p0583 expires, then r0587 is set to the
maximum measuring time.
Dependency:
Refer to: p0580
Note:
For p0580 = 0 (no measuring probe), a value of zero is displayed here.
Description:
Displays the number of measuring pulses that have occurred (been received) up until now.
Dependency:
Refer to: p0580
Note:
After reaching 4294967295 (2^32 - 1), the counter starts again at 0.
Description:
Displays the time since the last measuring pulse was detected.
The delay time is specified as 32-bit value with a resolution of 1/48 µs.
When a measuring pulse occurs (is received) the delay time is reset and is limited to the maximum measuring time in
p0583.
Dependency:
Refer to: p0580
Note:
For p0580 = 0 (no measuring probe), a value of zero is displayed here.
Description:
Selects the units for the parameters of the technology controller.
For p0595 = 1, 2, the reference quantity set in p0596 is not active.
Value:
1:
%
2:
1 referred no dimensions
3:
bar
4:
°C
5:
Pa
6:
ltr/s
7:
m³/s
8:
ltr/min
9:
m³/min
10:
ltr/h
r0587
CO: Measuring probe measuring time measured / MT t_meas measured
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
r0588
CO: Measuring probe pulse counter / MT pulse counter
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
r0589
Measuring probe delay time / MT t_delay
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
p0595
Technological unit selection / Tech unit select
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
C(5)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
1 47
1
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......