SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
29
2 Parameters
2.2 List of parameters
Description:
Display of the calculated and smoothed rotor speed.
Frequency components from the slip compensation (for induction motors) are not included.
r0022 is identical to r0021, however, it always has units of rpm and contrary to r0021 cannot be changed over.
Dependency:
Refer to: r0021, r0063
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The speed actual value is available smoothed (r0021, r0022) and unsmoothed (r0063).
Description:
Display of the smoothed output frequency.
Frequency components from the slip compensation (for induction motors) are included.
Dependency:
Refer to: r0066
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The output frequency is available smoothed (r0024) and unsmoothed (r0066).
Description:
Displays the smoothed output voltage of the power unit.
Dependency:
Refer to: r0072
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The output voltage is available smoothed (r0025) and unsmoothed (r0072).
Description:
Displays the smoothed actual value of the DC link voltage.
Dependency:
Refer to: r0070
Notice:
When measuring a DC link voltage < 200 V, for the Power Module a valid measured value is not supplied. In this
case, when an external 24 V power supply is connected, a value of approx. 24 V is displayed in the display
parameter.
r0022
Speed actual value rpm smoothed / n_act rpm smooth
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
6799
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
r0024
Output frequency smoothed / f_outp smooth
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
6300, 6799
Min Max
Factory
setting
- [Hz]
- [Hz]
- [Hz]
r0025
CO: Output voltage smoothed / U_outp smooth
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2001
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
5730, 6300, 6799
Min Max
Factory
setting
- [Vrms]
- [Vrms]
- [Vrms]
r0026
CO: DC link voltage smoothed / Vdc smooth
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2001
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
6799
Min Max
Factory
setting
- [V]
- [V]
- [V]
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......