4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G120D
926
List Manual (LH14), 01/2016, A5E33842313
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- upgrade firmware to later version.
- contact Technical Support.
F30665
SI P2: System is defective
Message class:
Hardware/software error (1)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A system defect was detected before the last boot or in the actual one. The system might have been rebooted
(reset).
Fault value (r0949, interpret hexadecimal):
200000 hex, 400000 hex:
- fault in the actual booting/operation.
Additional values:
- defect before the last time that the system booted.
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- upgrade firmware to later version.
- contact Technical Support.
For fault value = 400000 hex:
- ensure that the Control Unit is connected to the Power Module.
A30666 (F)
SI Motion P2: Steady-state (static) 1 signal at the F-DI for safe acknowledgment
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
A logical 1 signal is present at the F-DI configured in p10106 for more than 10 seconds.
If, at the F-DI no acknowledgment was performed for safe acknowledgment, then a steady-state logical and 0 signal
must be present. This avoids unintentional safety-relevant acknowledgment (or the "Internal Event Acknowledge"
signal) if a wire breaks or one of the two digital inputs bounces.
Remedy:
Set the fail-safe digital input (F-DI) to a logical 0 signal (p10106).
Note:
F-DI: Failsafe Digital Input
F30680
SI Motion P2: Checksum error safety monitoring functions
Message class:
Safety monitoring channel has identified an error (10)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The actual checksum calculated by processor 2 and entered in r9398 over the safety-relevant parameters does not
match the reference checksum saved in p9399 at the last machine acceptance.
Safety-relevant parameters have been changed or a fault is present.
Note:
This fault results in a STOP A that can be acknowledged.
Fault value (r0949, interpret decimal):
0: Checksum error for SI parameters for motion monitoring.
1: Checksum error for SI parameters for component assignment.
Remedy:
- check the safety-relevant parameters and if required, correct.
- set the reference checksum to the actual checksum.
- execute the function "Copy RAM to ROM".
- perform a POWER ON if safety parameters requiring a POWER ON have been modified.
- carry out an acceptance test.
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......