SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
289
2 Parameters
2.2 List of parameters
Description:
Sets the signal source for the connector-binector converter.
A PZD receive word can be selected as signal source. The signals are available to be serially passed-on
(interconnection).
Dependency:
Refer to: r2094, r2095
Note:
From the signal source set via the connector input, the corresponding lower 16 bits are converted.
p2099[0...1] together with r2094.0...15 and r2095.0...15 forms two connector-binector converters:
Connector input p2099[0] to binector output in r2094.0...15
Connector input p2099[1] to binector output in r2095.0...15
Description:
Selects the faults for which the fault response should be changed
Dependency:
The fault is selected and the required response is set under the same index.
Refer to: p2101
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
Description:
Sets the fault response for the selected fault.
Value:
0:
NONE
1:
OFF1
2:
OFF2
3:
OFF3
5:
STOP2
6:
Internal armature short-circuit / DC braking
Dependency:
The fault is selected and the required response is set under the same index.
Refer to: p2100
Notice:
For the following cases, it is not possible to re-parameterize the fault response to a fault:
- fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- fault response is not permissible for the set fault number.
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
The fault response can only be changed for faults with the appropriate identification.
Example:
F12345 and fault response = NONE (OFF1, OFF2)
--> The fault response NONE can be changed to OFF1 or OFF2.
For value = 1 (OFF1):
Braking along the ramp-function generator down ramp followed by a pulse inhibit.
p2099[0...1]
CI: Connector-binector converter signal source / Con/bin S_src
Access level:
3
Calculated:
-
Data type:
U32 / Integer16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2468
Min Max
Factory
setting
- - 0
p2100[0...19]
Change fault response fault number / Chng resp F_no
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8050, 8075
Min Max
Factory
setting
0 65535
0
p2101[0...19]
Change fault response response / Chng resp resp
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8050, 8075
Min Max
Factory
setting
0 6 0
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......