2 Parameters
2.2 List of parameters
SINAMICS G120D
296
List Manual (LH14), 01/2016, A5E33842313
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
The acknowledge mode can only be changed for faults with the appropriate identification.
Example:
F12345 and acknowledge mode = IMMEDIATELY (POWER ON)
--> The acknowledge mode can be changed from IMMEDIATELY to POWER ON.
Description:
Sets the faults/alarms for which a trigger signal should be generated in r2129.0...15.
Dependency:
If the fault/alarm set in p2128[0...15] occurs, then the particular binector output r2129.0...15 is set.
Refer to: r2129
Description:
Display and BICO output for the trigger signals of the faults/alarms set in p2128[0...15].
Dependency:
If the fault/alarm set in p2128[0...15] occurs, then the particular binector output r2129.0...15 is set.
Refer to: p2128
Note:
CO: r2129 = 0 --> None of the selected messages has occurred.
CO: r2129 > 0 --> At least one of the selected messages has occurred.
Description:
Displays the system runtime in days when the fault occurred.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2109, r2133, r2136
Notice:
The time comprises r2130 (days) and r0948 (milliseconds).
The value displayed in p2130 refers to 01.01.1970.
p2128[0...15]
Faults/alarms trigger selection / F/A trigger sel
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8050, 8070
Min Max
Factory
setting
0 65535
0
r2129.0...15
CO/BO: Faults/alarms trigger word / F/A trigger word
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8070
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Trigger signal p2128[0]
ON
OFF
-
01
Trigger signal p2128[1]
ON
OFF
-
02
Trigger signal p2128[2]
ON
OFF
-
03
Trigger signal p2128[3]
ON
OFF
-
04
Trigger signal p2128[4]
ON
OFF
-
05
Trigger signal p2128[5]
ON
OFF
-
06
Trigger signal p2128[6]
ON
OFF
-
07
Trigger signal p2128[7]
ON
OFF
-
08
Trigger signal p2128[8]
ON
OFF
-
09
Trigger signal p2128[9]
ON
OFF
-
10
Trigger signal p2128[10]
ON
OFF
-
11
Trigger signal p2128[11]
ON
OFF
-
12
Trigger signal p2128[12]
ON
OFF
-
13
Trigger signal p2128[13]
ON
OFF
-
14
Trigger signal p2128[14]
ON
OFF
-
15
Trigger signal p2128[15]
ON
OFF
-
r2130[0...63]
Fault time received in days / t_fault recv days
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8060
Min Max
Factory
setting
- - -
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......