SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
855
4 Faults and alarms
4.2 List of faults and alarms
A02060
Trace: Signal to be traced missing
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
- a signal to be traced was not specified.
- the specified signals are not valid.
Remedy:
- specify the signal to be traced.
- check whether the relevant signal can be traced.
A02061
Trace: Invalid signal
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
- the specified signal does not exist.
- the specified signal can no longer be traced (recorded).
Remedy:
- specify the signal to be traced.
- check whether the relevant signal can be traced.
A02062
Trace: Invalid trigger signal
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
- a trigger signal was not specified.
- the specified signal does not exist.
- the specified signal is not a fixed-point signal.
- the specified signal cannot be used as a trigger signal for the trace.
Remedy:
Specify a valid trigger signal.
A02063
Trace: Invalid data type
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The specified data type to select a signal using a physical address is invalid.
Remedy:
Use a valid data type.
A02070
Trace: Parameter cannot be changed
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The trace parameter settings cannot be changed when the trace is active.
Remedy:
- stop the trace before parameterization.
- if required, start the trace.
A02075
Trace: Pretrigger time too long
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected pretrigger time must be shorter than the trace time.
Remedy:
Check the pretrigger time setting and change if necessary.
F02080
Trace: Parameterization deleted due to unit changeover
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The trace parameterization in the drive unit was deleted due to a unit changeover or a change in the reference
parameters.
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......