2 Parameters
2.2 List of parameters
SINAMICS G120D
110
List Manual (LH14), 01/2016, A5E33842313
The following applies from firmware version 4.7 SP6 and p0612.8 = 1:
- p5390: when commissioning a catalog motor for the first time, p0605 is copied to p5390.
- p5390: p5390 is of significance when evaluating the alarm threshold.
- p5390: the stator winding temperature (r0632) is used to initiate the signal.
- p0627: when a catalog motor is commissioned for the first time, p0605 -40 °C is copied to p0627.
- p0627: p0627 is of significance for the rated temperature.
Motor temperature model 2 (p0612.1 = 1) or measurement:
- sets the fault threshold. If the temperature (r0035) exceeds the fault threshold, then fault F07011 is output.
Dependency:
Refer to: r0034, p0606, p0611, p0612
Refer to: F07011, A07012
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Motor temperature model 1 (I2t):
The following applies for firmware version < 4.7 SP6 or p0612.8 = 0:
p0605 also defines the final temperature of the model for r0034 = 100 %. Therefore, p0605 has no influence on the
time up to alarm A07012 being issued. The time is only determined by time constant p0611, the actual current and
the reference value p0318. For p0318 = 0, the rated motor current is used as reference value.
Note:
The hysteresis is 2 K.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
Description:
Sets the timer for monitoring the motor temperature for motor temperature model 2 or KTY/PT1000.
This timer is started when the temperature alarm threshold (p0604) is exceeded.
If the timer has expired and the alarm threshold has, in the meantime, not been fallen below, then fault F07011 is
output.
If the temperature fault threshold (p0605) is prematurely exceeded before the timer has expired, then fault F07011 is
immediately output.
Dependency:
Refer to: p0604, p0605
Refer to: F07011, A07910
Note:
With p0606 = 0 s, the timer is de-activated and only the fault threshold is effective.
KTY/PT1000: When setting the minimum value, the timer is disabled and a fault is not output until p0605 is
exceeded.
PTC, bimetallic NC contact: The timer minimum value has no special significance.
Description:
Sets the timer between the output of alarm and fault for a temperature sensor fault.
If there is a sensor fault, this timer is started.
If the sensor fault is still present after the timer has expired, a corresponding fault is output.
Notice:
The parameterized time is internally rounded-off to an integer multiple of 48 ms.
Note:
If the motor is an induction motor, the timer is switched off when setting the minimum value and no alarm is output.
Temperature monitoring is then based on the thermal model.
p0606[0...n]
Mot_temp_mod 2/sensor timer / Mod 2/sens timer
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(3), U, T
Scaling:
-
Dyn. index:
MDS
Unit group:
-
Unit selection:
-
Func. diagram:
8016
Min Max
Factory
setting
0.000 [s]
600.000 [s]
0.000 [s]
p0607[0...n]
Temperature sensor fault timer / Sensor fault time
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(3), U, T
Scaling:
-
Dyn. index:
MDS
Unit group:
-
Unit selection:
-
Func. diagram:
8016
Min Max
Factory
setting
0.000 [s]
600.000 [s]
0.100 [s]
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......