SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
435
2 Parameters
2.2 List of parameters
Description:
Sets the function specification for the safe motion monitoring.
Value:
1:
Safety without encoder and braking ramp(SBR)
3:
Safety without encoder with accel_monitoring(SAM) / delay time
Dependency:
Refer to: C30711
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Description:
Sets the function configuration for safe motion monitoring.
Dependency:
Refer to: C01711
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
For bit 00:
When the function is activated, a safety-relevant acknowledgment (internal event acknowledge) can be performed by
selecting/deselecting STO.
For bit 01:
When the function is activated, the active setpoint velocity limit (CO: r9733) is set to zero when STOP F is active.
Description:
Sets the behavior of safety functions and their feedback during pulse suppression in encoderless operation.
Dependency:
Refer to: C01711
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
For bit 00:
If the OFF1 or the OFF3 ramp-down time is too low, or there is an insufficient clearance between the SSM limit
speed, and the shutdown speed, then it is possible that the "speed under limit value" signal does not change to 1,
because no speed actual value below the SSM limit was able to be identified before pulse cancellation. In this case,
the OFF1 or the OFF3 ramp-down time or the clearance between the SSM limit speed and shutdown speed must be
increased.
Note:
SDI: Safe Direction (safe motion direction)
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
p9306
SI Motion function specification (processor 2) / SI Mtn fct spec P2
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
1 3 1
p9307
SI Motion function configuration (processor 2) / SI Mtn config P2
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - 0011
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Extended message acknowledgment
Yes
No
-
01
Setpoint velocity limit for STOP F
No
Yes
-
p9309
SI Motion behavior during pulse suppression (processor 2) / SI Mtn behav IL P2
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-
-
0000 0000 1111 1111 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
SSM during pulse suppression and
sensorless
Becomes inactive
Remains active
-
08
SDI during pulse suppression and
sensorless
Becomes inactive
Remains active
-
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......