2 Parameters
2.2 List of parameters
SINAMICS G120D
524
List Manual (LH14), 01/2016, A5E33842313
Index:
[0] = Input pulse I
[1] = Reset input R
Description:
Setting parameter for pulse duration T in milliseconds of instance PST 0 of the pulse extension element.
Description:
Display parameter for output pulse Q of instance PST 0 of the pulse extension element.
Description:
Setting parameter for the run-time group in which the instance PST 0 of the pulse extension element is to be called.
Value:
5:
Run-time group 5
6:
Run-time group 6
9999: Do not calculate
Description:
Setting parameter for the run sequence of instance PST 0 within the run-time group set in p20181.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description:
Sets the signal source for input pulse I and the reset input R of instance PST 1 of the pulse extension element.
Index:
[0] = Input pulse I
[1] = Reset input R
p20179
PST 0 pulse duration in ms / PST 0 pulse_dur ms
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7234
Min Max
Factory
setting
0.00 5400000.00
0.00
r20180
BO: PST 0 output Q / PST 0 output Q
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7234
Min Max
Factory
setting
- - -
p20181
PST 0 run-time group / PST 0 RTG
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7234
Min Max
Factory
setting
5 9999
9999
p20182
PST 0 run sequence / PST 0 RunSeq
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7234
Min Max
Factory
setting
0 7999
490
p20183[0...1]
BI: PST 1 inputs / PST 1 inputs
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7234
Min Max
Factory
setting
- - 0
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......