2 Parameters
2.2 List of parameters
SINAMICS G120D
176
List Manual (LH14), 01/2016, A5E33842313
Description:
Sets the smoothed response to the OFF1 command or the reduced setpoint for the extended ramp-function
generator.
Value:
0:
Cont smoothing
1:
Discont smoothing
Dependency:
No effect up to initial rounding-off time (p1130) > 0 s.
Note:
p1134 = 0 (continuous smoothing)
If the setpoint is reduced while ramping-up, initially a final rounding-off is carried out and then the ramp-up
completed. During the final rounding-off, the output of the ramp-function generator continues to go in the direction of
the previous setpoint (overshoot). After the final rounding-off has been completed, the output goes toward the new
setpoint.
p1134 = 1 (discontinuous smoothing)
If the setpoint is reduced while ramping-up, then the output goes immediately in the direction of the new setpoint. For
the setpoint change there is no rounding-off.
Description:
Sets the ramp-down time from the maximum speed down to zero speed for the OFF3 command.
Note:
This time can be exceeded if the DC link voltage reaches its maximum value.
Description:
Sets the initial rounding-off time for OFF3 for the extended ramp generator.
Description:
Sets the final rounding-off time for OFF3 for the extended ramp generator.
Description:
Sets the signal source for scaling the ramp-up time of the ramp-function generator.
Dependency:
Refer to: p1120
p1134[0...n]
Ramp-function generator rounding-off type / RFG round-off type
Access level:
2
Calculated:
-
Data type:
Integer16
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
3070
Min Max
Factory
setting
0 1 0
p1135[0...n]
OFF3 ramp-down time / OFF3 t_RD
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(1), U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
3060, 3070
Min Max
Factory
setting
0.000 [s]
5400.000 [s]
0.000 [s]
p1136[0...n]
OFF3 initial rounding-off time / RFGOFF3 t_strt_rnd
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
3070
Min Max
Factory
setting
0.000 [s]
30.000 [s]
0.000 [s]
p1137[0...n]
OFF3 final rounding-off time / RFG OFF3 t_end_del
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
3070
Min Max
Factory
setting
0.000 [s]
30.000 [s]
0.000 [s]
p1138[0...n]
CI: Ramp-function generator ramp-up time scaling / RFG t_RU scal
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
PERCENT
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
3060, 3070
Min Max
Factory
setting
- - 1
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......