4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G120D
854
List Manual (LH14), 01/2016, A5E33842313
A02051
Trace: recording not possible as a result of know-how protection
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
TRACE recording is not possible as at least one signal or trigger signal being used is under know-how protection.
Alarm value (r2124, interpret decimal):
1: Recorder 0
2: Recorder 1
3: Recorders 0 and 1
Remedy:
- Temporarily activate or de-activate know-how protection (p7766).
- include the signal in the OEM exception list (p7763, p7764).
- Where relevant do not record the signal.
See also: p7763 (KHP OEM exception list number of indices for p7764), p7764 (KHP OEM exception list)
A02055
Trace: Recording time too short
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The trace duration is too short.
The minimum is twice the value of the trace clock cycle.
Remedy:
Check the selected recording time and, if necessary, adjust.
A02056
Trace: Recording cycle too short
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected recording cycle is shorter than the selected basic clock cycle 0 (p0110[0]).
Remedy:
Increase the value for the trace cycle.
A02057
Trace: Time slice clock cycle invalid
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The time slice clock cycle selected does not match any of the existing time slices.
Remedy:
Enter an existing time slice clock cycle. The existing time slices can be read out via p7901.
See also: r7901 (Sampling times)
A02058
Trace: Time slice clock cycle for endless trace not valid
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected time slice clock cycle cannot be used for the endless trace
Remedy:
Enter the clock cycle of an existing time slice with a cycle time >= 2 ms for up to 4 recording channels or >= 4 ms
from 5 recording channels per trace.
The existing time slices can be read out via p7901.
See also: r7901 (Sampling times)
A02059
Trace: Time slice clock cycle for 2 x 8 recording channels not valid
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected time slice clock cycle cannot be used for more than 4 recording channels.
Remedy:
Enter the clock cycle of an existing time slice with a cycle time >= 4 ms or reduce the number of recording channels
to 4 per trace.
The existing time slices can be read out via p7901.
See also: r7901 (Sampling times)
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......