SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
873
4 Faults and alarms
4.2 List of faults and alarms
A07463 (F)
EPOS: External block change not requested in the traversing block
Message class:
Application/technological function faulted (17)
Reaction:
NONE
Acknowledge:
NONE
Cause:
For a traversing block with the block change enable CONTINUE_EXTERNAL_ALARM, the external block change
was not requested.
Alarm value (r2124, interpret decimal):
Number of the traversing block.
Remedy:
Resolve the reason as to why the edge is missing at binector input (BI: p2632).
F07464
EPOS: Traversing block is inconsistent
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The traversing block does not contain valid information.
Fault value (r0949, interpret decimal):
Number of the traversing block with invalid information.
Remedy:
Check the traversing block and where relevant, take into consideration alarms that are present.
A07465
EPOS: Traversing block does not have a subsequent block
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
There is no subsequent block in the traversing block.
Alarm value (r2124, interpret decimal):
Number of the traversing block with the missing subsequent block.
Remedy:
- parameterize this traversing block with the block change enable END.
- parameterize additional traversing blocks with a higher block number and for the last block, using the block change
enable END.
A07466
EPOS: Traversing block number assigned a multiple number of times
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The same traversing block number was assigned a multiple number of times.
Alarm value (r2124, interpret decimal):
Number of the traversing block that was assigned a multiple number of times.
Remedy:
Correct the traversing blocks.
A07467
EPOS: Traversing block has illegal task parameters
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The task parameter in the traversing block contains an illegal value.
Alarm value (r2124, interpret decimal):
Number of the traversing block with an illegal task parameter.
Remedy:
Correct the task parameter in the traversing block.
A07468
EPOS: Traversing block jump destination does not exist
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
In a traversing block, a jump was programmed to a non-existent block.
Alarm value (r2124, interpret decimal):
Number of the traversing block with a jump destination that does not exist.
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......