SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
837
4 Faults and alarms
4.2 List of faults and alarms
For fault value = 21:
- use a Power Module that supports the Safety Integrated functions.
For fault value = 26:
- de-activate the simulation mode for the set signal source for STO (p9620) (p0795).
- de-activate the simulation mode (p0795) for the F-DIs used by the Safety Integrated functions (r10049, p10006,
p10009).
- For the set test stop of the F-DO with feedback signal input (p10046, p10047), check the simulation mode, and if
required, de-activate (p0795).
For fault value = 28: use the power unit with the feature "STO via terminals at the Power Module".
Note:
F-DI: Failsafe Digital Input
STO: Safe Torque Off
See also: p9501, p9601, p9761, p9801
F01660
SI P1 (CU): Safety-related functions not supported
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The Power Module does not support the safety-related functions. Safety Integrated cannot be commissioned.
Note:
This fault does not result in a safety stop response.
Remedy:
- use a Power Module that supports the safety-related functions.
F01661
SI P1 (CU): Simulation of the safety inputs active
Message class:
General drive fault (19)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The simulation of the digital inputs of the Control Unit (p0795) is active.
It is not permissible that safety inputs are simulated.
Fault value (r0949, interpret binary):
The displayed bits indicate which digital inputs must not be simulated.
Remedy:
- de-activate the simulation of the digital inputs of the Control Unit for the safety inputs (p0795).
- acknowledge fault.
F01662
Error internal communications
Message class:
Hardware/software error (1)
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
A module-internal communication error has occurred.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- upgrade firmware to later version.
- contact Technical Support.
F01663
SI P1 (CU): Copying the SI parameters rejected
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
In p9700, the value 87 or 208 is saved or was entered offline.
This is the reason that when booting, an attempt is made to copy Safety Integrated parameters from processor 1 to
processor 2. However, no safety-relevant function has been selected on processor 1 (p9501 = 0, p9601 = 0). This is
the reason that copying is not possible.
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......