2 Parameters
2.2 List of parameters
SINAMICS G120D
310
List Manual (LH14), 01/2016, A5E33842313
Description:
Sets the delay time to evaluate the load monitoring.
Description:
Sets the load monitoring configuration.
Value:
0:
Monitoring switched out
1:
Monitoring torque and load drop
2:
Monitoring speed and load drop
3:
Monitoring load drop
Dependency:
Refer to: p2182, p2183, p2184, p2185, p2186, p2187, p2188, p2189, p2190, p2192, r2198, p3230, p3231, p3232
Refer to: A07920, A07921, A07922, F07923, F07924, F07925, F07936
Description:
Sets the torque threshold value for the message "Torque utilization < torque threshold value 2" (BO: r2199.11).
The message "torque setpoint < p2174" (BO: r2198.10) and "torque utilization < p2194" (BO: r2199.11) are only
evaluated after the run-up and the delay time has expired.
Dependency:
Refer to: r0033, p2195, r2199
Description:
Sets the switch-off delay time for the negated signal "run-up completed".
The message "torque setpoint < p2174" (BO: r2198.10) and "torque utilization < p2194" (BO: r2199.11) are only
evaluated after the run-up and the delay time has expired.
Dependency:
Refer to: p2174, p2194
Description:
Sets the scaling factor for torque utilization (r0033).
p2192[0...n]
Load monitoring delay time / Load monit t_del
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
8013
Min Max
Factory
setting
0.00 [s]
65.00 [s]
10.00 [s]
p2193[0...n]
Load monitoring configuration / Load monit config
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
8013
Min Max
Factory
setting
0 3 1
p2194[0...n]
Torque threshold value 2 / M_thresh val 2
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
8012
Min Max
Factory
setting
0.00 [%]
100.00 [%]
90.00 [%]
p2195[0...n]
Torque utilization switch-off delay / M_util t_off
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
8012
Min Max
Factory
setting
0.0 [ms]
1000.0 [ms]
800.0 [ms]
p2196[0...n]
Torque utilization scaling / M_util scal
Access level:
1
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(1, 3), U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.00 [%]
1000.00 [%]
100.00 [%]
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......