SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
231
2 Parameters
2.2 List of parameters
Description:
Sets the smoothing time for the flux setpoint in the field-weakening range
Recommendation:
Smoothing should be especially used if there is no regenerative feedback into the line supply. This means that the
DC link voltage can quickly increase in regenerative operation
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Note:
Only the flux setpoint rise is smoothed
Description:
Sets the scaling of the pre-control characteristic for the start of field weakening.
For values above 100 % and for partial load situations, the field weakening starts at higher speeds.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Note:
If the start of field weakening is shifted to lower speeds, then the voltage reserve is increased for partial load
situations.
If the start of field weakening is shifted to higher speeds, the voltage reserve is appropriately reduced so that for fast
load changes, it can be expected that this will have a negative impact on the dynamic performance.
Description:
Displays the pre-control value for the field weakening current.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description:
Sets the proportional gain for the flux controller.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Note:
The value is automatically pre-assigned dependent on the motor when the drive system is first commissioned.
When calculating controller parameters (p0340 = 4), this value is re-calculated.
p1584[0...n]
Field weakening operation flux setpoint smoothing time / Field weak T_smth
Access level:
4
Calculated:
p0340 = 1,3
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6722
Min Max
Factory
setting
0 [ms]
20000 [ms]
0 [ms]
p1586[0...n]
Field weakening characteristic scaling / Field weak scal
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
80.0 [%]
120.0 [%]
100.0 [%]
r1589
Field-weakening current pre-control value / I_FieldWeak prectr
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2002
Dyn. index:
-
Unit group:
6_2
Unit selection:
p0505
Func. diagram:
6724
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]
p1590[0...n]
Flux controller P gain / Flux controller Kp
Access level:
4
Calculated:
p0340 = 1,3,4
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6723
Min Max
Factory
setting
0.0 999999.0
10.0
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......