2 Parameters
2.2 List of parameters
SINAMICS G120D
372
List Manual (LH14), 01/2016, A5E33842313
The following applies for "positioning":
Using binector inputs p2651 and p2652, when the modulo correction (BI: p2577 = 1 signal) is activated and for
absolute positioning (BI: p2648 = 1 signal), the traversing direction is specified as follows:
BI: p2651 / BI: p2652
0 signal / 0 signal: Absolute positioning through the shortest distance.
1 signal / 0 signal: Absolute positioning in the positive direction.
0 signal / 1 signal: Absolute positioning in the negative direction.
1 signal / 1 signal: Absolute positioning through the shortest distance.
Description:
Sets the signal source for setting-up in the operating mode "direct setpoint input/MDI".
BI: p2653 = 1 signal
Setting-up selected.
BI: p2653 = 0 signal
Positioning selected.
Dependency:
Refer to: p2651, p2652
Note:
In the operating mode "direct setpoint input/MDI", it is possible to make a flying changeover between setting-up and
positioning.
For "setup" (BI: p2653 = 1 signal), the following applies:
A traversing direction must be selected via binector inputs p2651 and p2652.
Description:
Sets the signal source to interconnect the MDI mode to the operating mode "direct setpoint input MDI" via
PROFIBUS telegram 110.
CI: p2654 = 0
The binector inputs listed below are evaluated.
CI: p2654 > 0
The following binector inputs are not evaluated:
- BI: p2648 (positioning type)
- BI: p2651 (direction selection, positive)
- BI: p2652 (direction selection, negative)
In this case, the following definitions apply:
Signal via CI: p2654 = xx0x hex -> absolute
Signal via CI: p2654 = xx1x hex -> relative
Signal via CI: p2654 = xx2x hex -> abs_pos (only for modulo correction)
Signal via CI: p2654 = xx3x hex -> abs_neg (only for modulo correction)
Dependency:
Refer to: p2648, p2651, p2652
p2653
BI: EPOS direct setpoint input/MDI setting-up selection / MDI setting-up sel
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
1
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3620
Min Max
Factory
setting
- - 0
p2654
CI: EPOS direct setpoint input/MDI mode adaptation / MDI mode adapt
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
1
Calculated:
-
Data type:
U32 / Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3620
Min Max
Factory
setting
- - 0
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......